Configuration | Rectifier Module | Monitoring Module | Distribution | Remark |
Standard | GPR4850D or GPR4850E 7pcs (max.) |
GPM48P (With Ethernet Port) | AC distribution: 3-phase, 4-wire input, 3-pole AC breaker @ general line (63A); DC distribution: Battery fuse 125A/2P; LVLD: 63A×4 32A×3 16A×4 (MCB capacity could change) LVBD: 16A×6 (MCB capacity could change) |
For details, please refer to the specifications of modules. |
Input | |||||
Parameters | Min. | Typ. | Max. | Unit | Remark |
Input voltage range | 90 | 220 | 285 | Vac | |
Input frequency | 45 | 50 | 65 | Hz | |
Input current | 40 | A | |||
Power factor | 0.98 | ||||
Input over voltage protection | 300 | Vac | Auto-recovery | ||
Input over voltage recovery | 280 | Vac | hysteresis width ≥5V | ||
Input low voltage protection | 85 | Vac | Auto-recovery | ||
Input low voltage recovery | 90 | Vac | hysteresis width ≥5V | ||
Input over current protection | MCB at input side as protection |
Output | |||||
Parameters | Min. | Typ. | Max. | Unit | Remark |
Output voltage range | 42 | 53.5 | 58 | Vdc | |
Output current range | 0 | 350 | A | 176~285VAC | |
0 | 75 | A | 90~175VAC | ||
Output power | 0 | 18725 | W | 176~285VAC total power=load power + battery power |
|
0 | 9350 | W | 90~175VAC | ||
Ripple (Vp-p) | 200 | mv | Rated input/output, apply 0.1uF film capacitor and 10uF high frequency electrolyte capacitor, oscilloscope band width of 20MHz. | ||
Output efficiency | 91 | 92 | % | 220Vac input | |
83 | % | 110Vac input | |||
Output over voltage protection | 58.5 | 60.5 | Vdc | Lock up | |
Output current limit protection | Available | ||||
Output short-circuit protection | Long time short-circuit no damage, auto-recovery | ||||
Over temperature protection | Auto-recovery when ambient temperature <65ºC | ||||
LVD | 2 LVD available, 1 for critical loads, 1 for battery bank | ||||
Battery anti-pole protection | Battery and power supply no damage | ||||
Voltage regulation | ±1 | % | |||
Basic output features (form 2) | |||||
Parameters | Min. | Typ. | Max. | Unit | Remark |
Temperature coefficient | ±0.2 | ‰/ºC | |||
Current share unbalance range | ±5 | % | @50~100% load | ||
System on-off Inrush voltage | ±5 | % | When plug out any rectifier module(load current should be higher than total rectifier output current), system voltage fluctuation | ||
dynamic response | 200 | uS | 25%~50%~25% load change 50%~75%~50% load change |
||
dynamic response adjustment | ±5 | % | Rated output voltage, rated load current | ||
Start power rise time | 3 | 8 | S | Time between system power on to rectifier output voltage rise to rated value | |
Inner voltage reduce | 500 | mV |