Customization: | Available |
---|---|
Output Type: | Single |
Warranty: | 2 Years |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Input | |||||
Parameter | Min. | Typical | Max. | Unit | Remark |
Input voltage range | 90 | 220 | 280 | Vac | |
Input frequency | 45 | 50 | 65 | Hz | |
Input current | 27 | A | |||
Power factor | 0.98 |
Output | |||||
Parameter | Min. | Typical | Max. | Unit | Remark |
Output voltage range | 42 | 53.5 | 58 | Vdc | |
Output current range | 0 | 30 | A | 176~280VAC | |
0 | 15 | A | 90~175VAC | ||
Ripple (Vp-p) | 200 | mv | Rated input/output, with 0.1uF film capacitor and 10uF high frequency electrolyte capacitor, oscilloscope band width of 20MHz. | ||
Output efficiency | 90 | % | 220Vac input | ||
83 | % | 110Vac input | |||
Regulation | ±1 | % | |||
Load regulation | ±1 | % | |||
Line regulation | ±1 | % |