Customization: | Available |
---|---|
Output Type: | Single |
Warranty: | 2 Years |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Environmental | |||||
Parameter | Min. | Typ. | Max. | Unit | Remark |
working temperature | -25 | 50 | °C | -30 ° C, power on | |
Storage temperature | -30 | 85 | °C | ||
relative humidity | 5 | 95 | % | ||
atmospheric pressure | 70 | 106 | KPa | ||
Sea level | 4000 | m | |||
Heat dissipation mode | Natural heat dissipation |
input | ||||||
Parameter | Min. | Typ. | Max. | Unit | Remark | |
Input voltage range | 150 | 220 | 280 | Vac | ||
212 | 396 | Vdc | ||||
Input frequency | 45 | 50 | 65 | Hz | ||
Input power factor | 0.95 | Rated input | ||||
output characteristic | |||||
Parameter | Min. | Typ. | Max. | Unit | Remark |
Output voltage range | -52 | -53.5 | -58 | Vdc | Rated input, test at full load |
Load output current | 15 | A | |||
Precision of voltage regulation | ±2 | % | |||
Load adjustment rate | ±1 | % | |||
Source adjustment rate | ±1 | % | |||
Ripple + noise | 200 | mV | |||
efficiency | 90 | % | 220VAC ± 20% / 310vdc ± 20% input, 100% rated output | ||
output power | 802 | W | |||
temperature coefficient | ±0.02% | /ºC | |||
Dynamic response overshoot | ±5 | % | 25% - 50% - 25% or 50% - 75% - 50% load change | ||
Dynamic response recovery time | 200 | us | 0.1A/ us | ||
Overshoot amplitude of switching machine | ±5 | % | |||
Soft start time | 8 | S | Rated input voltage switch to output voltage to set value |