Customization: | Available |
---|---|
Output Type: | Multiple |
Warranty: | 2 Years |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Input | |||||
Parameter | Min. | Typ. | Max. | Unit | Remark |
DC operating voltage range | 42 | 60 | Vdc | ||
Input rated voltage | 48 | Vdc | |||
Input rated current | 11 | 12 | 13 | A | Rated input, rated output |
Maximum Impulse Current Input on Start-up | 18 | A | Less than 150% of rated current |
output | ||||||
Parameter | Min. | Typ. | Max. | Unit | Remark | |
Output Voltage Range | 200 | 220 | 230 | Vac | Input full voltage range | |
Rated output voltage | 220 | Vac | ||||
Rated output current | 2.3 | A | ||||
Output Voltage Accuracy | ±4 | % | Input voltage (> 46Vdc) | |||
Rated Output Frequency | 49 | 50 | 51 | Hz | ||
Rated capacity | 500 | VA | ||||
Rated output power | 400 | W | ||||
Whole machine efficiency | 86 | % | Rated working conditions | |||
Output power factor | 0.8 | Rated working conditions | ||||
Dynamic transient recovery time | 60 | ms | ||||
wave form | Sinusoidal THD < 3% (Linear Load) | |||||
Sinusoidal THD < 8% (Nonlinear Load) | ||||||
Overload capacity | 105-125% lasts no less than 60 seconds, 125-150% lasts no less than 10 seconds (input voltage (> 48Vdc) | |||||
Peak Coefficient of Output Current | 3:1 | |||||
Output mode | One way AC output |