Input | ||||||
Item | Min | Typical | Max | Unit | Note | |
DC Charger | Input Voltage | 100 | 300 | Vdc | ||
Output Rated Voltage | 48 | Vdc | ||||
Output Current | 30 | A | ||||
AC Charger | Input Voltage | 90 | 220 | 280 | Vac | |
Input Rated Voltage | 120 | Vac | ||||
Input voltage frequency | 57 | 60 | 63 | Hz | ||
Power Factor | 0.99 | |||||
Output Voltage | 48 | Vdc | ||||
Output Current | 50 | A |
Output | ||||||
Item | Min | Typical | Max | Unit | Note | |
AC(OUT) Inverter | Output voltage | 115 | 120 | 125 | Vac | |
Output Rated Voltage | 120 | Vac | ||||
Output Voltage Frequency | 57 | 60 | 63 | Hz | ||
Output Current | 30 | A | ||||
AC Bypass | Output Rated Voltage | 90 | 164 | Vac | AC first | |
Output Voltage Frequency | 60 | |||||
Output Current | 30 | A | ||||
BAT+ BAT-(OUT) | Output Voltage | 48 | Vdc | BAT output directly, with protection of short and current limit | ||
Output Current | 5 | A | ||||
DC1+ DC2+ DC3+ GND(OUT) | Output Voltage | 300 | Vdc | There's equipped with output interface and the user can connect a certain load to absorb the excess power when the PV input exceeds the max DC charging |
Protection | ||||||
Item | Min | Typical | Max | Unit | Note | |
Each Module | Over Temperature | Output is cut off when the inside temperature of heat sink is up to the peak point, then it will reduce 10ºC | ||||
Output Over Current | Also protection of over power and short |
BMS | ||
Battery Management | DC Charger | MPPT, charge with the max power |
AC Charger | Constant current charge first, constant voltage charge later | |
Over/under Voltage Protection | With BMS itself |
Insulation | |||||
Item | Min | Typical | Max | Unit | Note |
Input-Cabinet | 2121 | Vdc | Only test DC charge, AC charger and inverter | ||
Input-Output | 2121 | Vdc | |||
Output-Cabinet | 750 | Vdc | |||
Isolated Resistance | All the isolated resistance of input-output, input-earth and output-earth is no less than 10MΩ under the situation of normal atmosphere, 90% humidity and 500Vdc test voltage. |
Environment | |||||
Item | Min | Typical | Max | Unit | Note |
Working Temperature | -10 | 40 | °C | ||
Extended Working Temperature | -20 | 50 | °C | ||
Storage Temperature | -10 | 60 | °C | ||
Humidity | 90 | % | |||
Atmosphere | 70 | 106 | KPa | ||
Altitude | 0 | 3000 | m | ||
Cooling | Fan | ||||
Dust Proof | Requirement of dust: diameter: >5um, density: ≤3×104pcs/m3, non-conductive, non-magnetic and non-caustic. No protection of water proof |