Customization: | Available |
---|---|
Output Type: | Single |
Warranty: | 2 Years |
Still deciding? Get samples of US$ 75/Piece
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Input | ||||||
Parameter | Min. | Typ | Max. | Unit | Remarks | |
Input Voltage Range | 90 | 220 | 280 | Vac | ||
Input Frequency | 45 | 50 | 65 | Hz | Rated load | |
Input Current | 6.8 | A | ||||
Power Factor | 0.98 | Rated input/rated load |
Output | |||||
Parameter | Min. | Typ. | Max. | Unit | Remarks |
Output Voltage Range | 36 | 53.5 | 58 | Vdc | |
Output Current Range | 0 | 15 | A | 176~280V ac Input | |
Regulation | ±1 | % | |||
Weighted Psophometric Noise | 2 | mV | |||
Wide Frequency Noise Voltage | 50 20 |
mV | (3.4KHz~150KHz) (150KHz~30MHz) |
||
Ripple (Vp-p) | 200 | mV | Rated input/output, with 0.1uF film capacitor and 10uF high frequency electrolyte capacitor, oscilloscope band width of 20MHz. | ||
Output Power | 0 | 800 | W | 176-280V input, see remark 1 | |
0 | 400 | W | 90-<176V input, see remark 1 | ||
Output Efficiency | >90 | % | 220V AC input | ||
>83 | % | 110V AC input |
Ambient requirements | |||||
Parameters | Min | Typ. | Max | Unit | Remark |
Operating temp | -20 | 55 | °C | @ 55ºC, system operates with full load +55~+65ºC linear derating of 2.0%/ºC, See remark 2 |
|
Extended operating temp | -20 | 65 | °C | ||
Storage tempStorage temperature | -40 | 70 | °C | ||
Humidity | 5 | 95 | % | Relative humidity, no condensing | |
Operating Altitude | -60 | 2500 | m | More than altitude 2500m(8200 ft.), max. operating temperature would decreases 2°C according to the upper altitude for every 305m(1000ft.) | |
-200 | 8200 | ft | |||
Expanding Operating Altitude | -60 | 4000 | m | ||
-200 | 13120 | ft | |||
Earthquake rating | 4 | Zone | |||
Acoustic noise | 50 | dB | In proportion to fan speed, load and ambient temperature | ||
Below requirements for test and operation temperature shall be reached: (1) @-22ºC, start up with rated power 800W during high voltage (176-280VAC); (2) @55ºC~65ºC, auto derating of power is recommended. @65ºC, at least 80% rated power will be regularly output for long time; (3) @55ºC, max output power will be conducted without over-temperature protection. The component shall normally operate with required strain. |