Customization: | Available |
---|---|
Output Type: | Single |
Warranty: | 2 Years |
Still deciding? Get samples of US$ 1200/Piece
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Configuration | Rectifier Module | Monitoring Module | Distribution | Remark |
Standard | GPR4850DR03 | GPM48P (With Ethernet Port) | AC Distribution: single phase AC control circuit breaker (100A/2P) *1; DC distribution: battery fuse 100A*4; LVD1: 63A*3, 32A*5, 16A*4 (MCB capacity is optional). LVD2: 32A*3, 16A*4 (MCB capacity is optional). |
For details, please refer to the specifications of modules. |
Input | |||||
Parameters | Min. | Typ. | Max. | Unit | Remark |
Input voltage range | 90 | 220 | 290 | Vac | |
Input frequency | 45 | 50 | 65 | Hz | |
Input current | 95 | A | |||
Power factor | 0.98 | Rated load | |||
Input over voltage protection | 300 | Vac | Auto-recovery | ||
Input over voltage recovery | 290 | Vac | Return difference ≥5V | ||
Input low voltage protection | 85 | Vac | Auto-recovery | ||
Input low voltage recovery | 90 | Vac | Return difference ≥5V | ||
Input over current protection | MCB at AC input side for protection |
Output | |||||
Parameters | Min. | Typ. | Max. | Unit | Remark |
Output voltage range | 42 | 53.5 | 58 | Vdc | Adjusting through monitor ,test with no load |
Output power | 0 | 18725 | W | Input 176-290Vac, 18725W output (Rated power including the sum of battery charging power and load power ) | |
0 | 9350 | W | Input 90-175Vac |
||
Output over voltage protection | 58.5 | 60.5 | Vdc | Lock up |
|
Output current limit protection | Available | ||||
Output short-circuit protection | Long time short-circuit no damage, auto-recovery | ||||
Over temperature protection | Auto-recovery @ ambient temperature <65ºC | ||||
Battery low voltage disconnection protection | Available | ||||
Battery anti-pole protection | Battery and power supply no damage | ||||
Voltage regulation | ±1 | % |