Customization: | Available |
---|---|
Rated Power: | 556W |
Charging Current: | 48V/10A |
Still deciding? Get samples of US$ 10/Piece
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Ambient | |||||
Parameters | Min | Typical | Max | Unit | Remark |
Operating temperature | -40 | 55 | °C | The charger is able to start @-40°C. | |
Extended operating temperature | 55 | 75 | °C | Auto derating | |
Storage temperature | -45 | 85 | °C | ||
Humidity | 5 | 95 | % | Relative humidity, no condensing | |
Altitude | -60 |
4000 |
m |
Horizontally, the unit operates with max temp of 65°C, which will derate 1.5°C per rise of 1000m. | |
-200 | 13000 | ft | If the operation is above 2500m (5000 ft), the max operation temperature derates 2°C. per rise of 305m (1000 ft.) |
||
Atmospheric pressure | 70 | 106 | KPa | ||
Cooling | Natural cooling | ||||
Noise | 45 | dB |
Input | |||||
Parameter | Min. | Typical | Max. | Unit | Remark |
Input voltage range | 90 | 120/230 | 300 | Vac | |
Input frequency | 45 | 50 | 65 | Hz | |
Input current (Max.) |
6.7 | A | 120Vac | ||
2.8 | A | 230Vac | |||
Inrush current | 13.3 | A | |||
Power Factor | 0.99 | Rated load, 120Vac | |||
0.98 | Rated load, 120Vac |
Output | |||||
Parameter | Min. | Typical | Max. | Unit | Remark |
Output voltage range | 40 | 56.5 | Vdc | ||
Output current range | 0 | 10 | A | ||
Load regulation | ±1 | % | |||
Regulation | ±1 | % | |||
Line regulation | ±0.5 | % | |||
Ripple (Vp-p) | 200 | mV | Rated input/output, with 0.1uF film capacitor and 10uF high frequency electrolyte capacitor applied, oscilloscope band width is 20MHz. | ||
Output power | 556 | W | Rated input/ full load output | ||
Output efficiency | 92 | % | Rated input/ full load output | ||
Start up time | 3 | 8 | S | Rise up to 40V~48V | |
Start up overshoot | 5 | % | |||
Transient response overshoot | ±5 | % | |||
Recovery time for transient response | 200 | us | 25%~50%~75% Load variation | ||
Temperature coefficient | ±0.02 | %/ºC | |||
Float charge voltage | 54 | V | |||
Equalizing charge voltage | 56.5 | V | |||
Temperature compensation | The voltage of equalizing/float charge decreases 60mV per 1ºC of rise when the temperature is more than 40ºC. |