95% high efficiency 50A rectifier for 48V telecom power system
Features
• Compact structure, high power density of 22W/in3 ;
• Constant current output available within output voltage 42-54V;
• Constant power output available within output voltage 54-58V ;
• Output voltage adjustable within 42-58Vdc
Default voltage: 53.5V;
• Wide operating temp. range: -33~+55°C
• Extended operating temp. range: +55~+65°C
• Power factor correction: ≥0.99
• RS485 communication port
• Input under-voltage protection
• Input over-voltage protection
• Output over-voltage protection
• Output over-current protection
• Over temperature alarm and protection
• Paralleled work available via current sharing bus
• Remote start up/shutdown
• Hot -swappable
• UL 60950, CSAC22.2 60950-00,
VDE0805 and IEC60950 compliance
• CE mark meets directives of 73/23/EEC
and 93/68/EEC
• High efficiency more than 95%
Applications
48V Distributed power system
Ethernet
Exchange
LAN, WAN
Server
Indoor wireless network
Telecom equipment
Input |
Parameter |
Min. |
Typ |
Max. |
Unit |
Remarks |
Input Voltage Range |
90 |
110/220 |
290 |
Vac |
|
Input Frequency |
45 |
50/60 |
65 |
Hz |
Rated load |
Input Current |
|
|
18.5 |
A |
|
Power Factor |
0.99 |
|
|
|
Rated input/rated load |
Output |
Parameter |
Min. |
Typ. |
Max. |
Unit |
Remarks |
Output Voltage Range |
42 |
53.5 |
58 |
Vdc |
Adjustable via the monitoring module (No load) |
53.5 |
|
53.8 |
Vdc |
220V Input, 25A Output |
Output Current Range |
0 |
|
50 |
A |
176~290V ac Input |
0 |
|
22 |
A |
90~175V ac Input |
Output Efficiency |
93 |
|
95 |
% |
220V AC Input (220Vac input, rated output voltage, 25% rated load current 94 |
93 |
|
95 |
% |
110V AC Input |
Output Power |
|
|
2900 |
W |
Input: 200-240Vac; Output: 53.5Vdc
|
|
|
1200 |
W |
Input: 115-130Vac; Output: 53.5Vdc; |
Regulation |
|
|
±1 |
% |
|
Weighted Psophometric Noise |
|
|
2 |
mV |
|
Wide Frequency Noise Voltage |
|
|
50 |
mV |
(3.4KHz~150KHz) |
|
|
20 |
(150KHz~30MHz) |
Ripple (Vp-p) |
|
|
200 |
mV |
Rated input voltage & load, with 0.1uF film capacitor and 10uF high frequency electrolyte capacitor, oscilloscope band width of 20MHz. |
Environmental Requirements |
Parameters |
Min |
Typ. |
Max |
Unit |
Remark |
Operating temp |
-33 |
|
55 |
°C |
|
Transportation temp |
-40 |
|
-70 |
°C |
|
Storage temp storage temperature |
-40 |
|
70 |
°C |
|
Humidity |
5 |
|
95 |
% |
Relative humidity, no condensing |
Altitude |
0 |
|
4000 |
m |
For operation at 3000-4000m, the operation temperature is derated by 1°C per 200m. |
Acoustic noise |
|
55 |
|
dB |
|
Cooling |
Forced cooling; Front-in & rear-out; the fan locates at front, with temperature controlled speed. |
About us: