Customization: | Available |
---|---|
Output Type: | Single |
Warranty: | 2 Years |
Still deciding? Get samples of US$ 700/Piece
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Configuration | Rectifier Module | Monitoring Module | Distribution | Remark |
Standard | GPR4850D | GPM48P (With Ethernet Port) | AC distribution: 3-phase, 4-wire input, 3-pole AC breaker @ general line (63A); DC distribution: Battery fuse 100A×2; LVLD: 63A×4 16A×4 LVBD: 10A×2 |
For details, please refer to the specifications of modules. |
Input | |||||
Parameter | Min. | Typical | Max. | Unit | Remark |
Input voltage range | 90 | 220 | 285 | Vac | |
Input frequency | 45 | 50 | 65 | Hz | |
Input current | 50 | A | |||
Power factor | 0.98 |
Output | |||||
Parameter | Min. | Typical | Max. | Unit | Remark |
Output voltage range | 42 | 53.5 | 58 | Vdc | |
Output current range | 0 | 150 | A | 176~285VAC | |
0 | 75 | A | 90~175VAC | ||
Ripple (Vp-p) | 200 | mv | Rated input/output, apply 0.1uF film capacitor and 10uF high frequency electrolyte capacitor, oscilloscope band width of 20MHz. |
||
Output efficiency | 90 | 92 | % | 220Vac input | |
83 | 85 | % | 110Vac input | ||
Regulation | ±1 | % | |||
Load regulation | ±1 | % | |||
Line regulation | ±1 | % |