Customization: | Available |
---|---|
Output Type: | Single |
Warranty: | 2 Years |
Still deciding? Get samples of US$ 2000/Piece
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Configuration | Rectifier Module | Max. | Distribution | Monitoring Module | Remark |
Option 1 | GPR4850E | 12 | AC distribution: 3 phases, 5 wires input, Class II/C SPDs; Triple-pole AC breaker @ general line ( 100A); Single-pole breaker @ rectifier input (20A*12) DC distribution: Battery fuse 400A*2; Primary shutdown: 100A*10 Secondary shutdown: 63A*2 32A*2 (MCB) |
GPM48A | For details, please refer to the specifications of modules. |
Input | |||||
Parameter | Min. | Typical | Max. | Unit | Remark |
Operating voltage rating | 110/220 | Vac | |||
Input voltage range | 90 | 220 | 290 | Vac | 3 phases, 5 wires input, Ph-Ph: 380V, Ph-Neutral line: 220VAC |
Input frequency | 43 | 50 | 67 | Hz | |
Battery input | 43.2 | 53.5 | 58 | Vdc | "+""-" of the battery group connected in parallel with DC output of rectifier module. (With identical polarity) |
Output | |||||
Parameter | Min. | Typical | Max. | Unit | Remark |
Output voltage range | 42 | 53.5 | 58 | Vdc | |
Output current range (Max current) | 0 | 600 | A | 170~285Vac input; The derating will be adopted for input voltage below 170Vac. |
|
Regulation | ±1 | % | |||
Load regulation | ±1 | % | |||
Line regulation | ±1 | % | |||
Current sharing | ±5 | % | |||
Battery output | 400A*2 | ||||
Ripple (Vp-p) | 200 | mv | Rated input/output, with 0.1uF film capacitor and 10uF high frequency electrolyte capacitor, oscilloscope band width of 20MHz. | ||
Output efficiency | 95 | % | 220Vac input |