Customization: | Available |
---|---|
Nature of Source Flow: | Solar PV Inverter |
Certification: | CCC, CE |
Still deciding? Get samples of US$ 300/Piece
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Model | GPDA3000VA-C | Remark | |
Item | Parameter | ||
DC Input | DC operating voltage range | 40~58Vdc | |
DC startup voltage range |
42~56Vdc | ||
Rated input voltage | 48Vdc | ||
Input current | 80A | rated input,rated output. | |
Startup Max. inrush input | 150A | ||
AC output | Rated output voltage | 220Vac | |
Rated output current | 1091A | power factor 0.8 | |
Output stabilized voltage precision | ±5% | ||
Rated output frequency | 50Hz | ||
Rated capacity | 3000VA | ||
Rated output power | 2400W | ||
output efficiency | 88% | Under rated operating conditions | |
output power factor | 0.8 | Under rated operating conditions | |
Dynamic transient recovery time | 100ms | ||
Voltage waveform | Sine wave THD<3% |
Linear load | |
Sine wave THD<8% |
Non-linear load | ||
Over load ability | 105 ~ 125% sustained no less than 60s, 125 ~ 150% sustained no less than 10s | ||
Output current peak coefficient | 3:1 | ||
Output method | Two national standard socket, a wiring output, each output of a single pole open control | ||
Inverse conversion bypass conversion time | <5ms | ||
Power supply priority mode | Inversion priority | ||
Protection | DC input under voltage protection point | 37~40 Vdc | with half load test |
DC input under voltage recovery point | 40~42 Vdc | Reached to the recovery value,auto recovery. | |
DC input over voltage protection point | 58~60 Vdc | with half load test | |
DC input over voltage recovery point | 56~58 Vdc | Reached to the recovery value,auto recovery. | |
Over temp. protection | When the main radiator temperature is too high, up to over-temperature protection point, turn off the output, the temperature hysteresis is about 10 ºC. | ||
Anti-reverse protection | When the input reverse, the power does not work, and no damage | ||
Short circuit protection | When a short circuit is detected, the power is turned off and an alarm signal is issued. It is automatically restarted every 30 seconds. After the fault is removed, it can be restored. Long-term short circuit, the power off lock, re-boot can work properly. | ||
Over current protection | When overcurrent is detected, the power is turned off and an alarm signal is issued. When the load returns to the rated value, it can be restored. Long-term overload, the power off lock, re-boot can resume normal work. | ||
Alarm function(sharp alarm) | DC input abnormal, overload, short circuit, inverter failure, the wind alarm, while warning lights. | ||
Ambient | Operating temp. | -5~+40ºC | |
Storage inverter temp. | -25~+70ºC | ||
Relative humidity | 0~95% | ||
Altitude | 3000m | ||
Cooling | Forced air cooling | ||
Operating ambient | No conductive explosion of dust, no corrosion and damage to the gas and steam, no severe vibration and shock. | ||
Insulation | Parameter | Standard requirement | Remark |
Dielectric strength | Input-output:2000Vac/10mA//1min | No flash, no breakdown | |
Input-earth:500Vdc/10mA//1min | |||
Output-earth:1500Vac/10mA//1mi | |||
Insulation resistance | At normal atmospheric pressure, the relative humidity of 95%, the test voltage is DC 500V, the power input to the output, input to the ground, the output to the ground insulation resistance of not less than 10MΩ. | ||
EMC | Conduction | comply to standard YD/T983-1998 A | |
Radiation | comply to standard YD/T983-1998 A | ||
Immunity | comply to standard YD/T983-1998 A | ||
Noise | <55dB(1meter) | ||
The shell protection level | IP20(indoor) | ||
Smell | No smell and other harmful smell to health | ||
Mechanical | Dimension | 481.6*270*88.1 mm | |
Weight | ≤4KG | ||