Customization: | Available |
---|---|
Warranty: | 2 Years |
Output Power: | 8300W |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Input | |||||
Item | Min. | Typical | Max. | Unit | Remark |
Input voltage range | 90 | 220 | 290 | Vac | |
Input frequency | 45 | 50 | 65 | Hz | |
Input current | 20 | A | |||
Power factor | 0.98 | Rated load | |||
Input over voltage protection | 300 | Vac | Automatically recoverable | ||
Input over voltage recovery | 290 | Vac | Return difference ≥5V | ||
Input under voltage protection | 85 | Vac | Automatically recoverable | ||
Input under voltage recovery | 90 | Vac | Return difference ≥5V | ||
Input over current protection | MCB in AC Input supplied protection |
Output | |||||
Item | Min. | Typical | Max. | Unit | Remark |
Output voltage range | 42 | 53.5 | 58 | Vdc | Adjustable by monitor, tested in no load |
Output power | 19000 | W | Make sure rated 4800W output when input voltage is 176~290VAC (rated power includes battery power plus load power) | ||
8300 | W | 90~175VAC input | |||
Output over voltage protection | 58.5 | 60.5 | Vdc | Lock up | |
Output current limiting protection | Current limiting protection | ||||
Output short circuit protection | Long-term short circuit protection, automatically recoverable | ||||
Over temperature protection | Automatically recoverable in normal temperature 65ºC | ||||
Battery power-down protection | Battery power-down protection | ||||
Battery polarities reversal connection protection | No damage on battery and power system | ||||
Voltage withstand efficiency | ±1 | % |