Customization: | Available |
---|---|
Output Type: | Single |
Warranty: | 2 Years |
Still deciding? Get samples of US$ 2000/Piece
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Configuration | Rectifier Module | Max. | Distribution | Monitoring Module | Remark |
Option | GPR4850D | 12 | AC distribution: 3 phases, 5 wires input, Class II/C SPDs; 3-pole AC input MCB 63A Single-pole breaker @ rectifier input (20A*12) AC output MCB: 3*16A(1P) 1*32A (3P) DC distribution: Battery fuse 250A*2; LVD1: 16*32A,8*63A LVD2: 5*16A, 5*32A, 3*63A |
GPM48A | For details, please refer to the specifications of modules. |
Input | |||||
Parameter | Min. | Typical | Max. | Unit | Remark |
Operating voltage rating | 110/220 | Vac | |||
Input voltage range | 90 | 220 | 290 | Vac | 3 phases, 5 wires input, Ph-Ph: 380V, Ph-Neutral line: 220VAC |
Input frequency | 43 | 50 | 67 | Hz | |
Battery input | 43.2 | 53.5 | 58 | Vdc | "+""-" of the battery group connected in parallel with DC output of rectifier module. (With identical polarity) |
Output | |||||
Parameter | Min. | Typical | Max. | Unit | Remark |
Output voltage range | 42 | 53.5 | 58 | Vdc | |
Output current range (Max current) | 0 | 600 | A | 170~285Vac input; The derating will be adopted for input voltage below 170Vac. |
|
Regulation | ±1 | % | |||
Load regulation | ±1 | % | |||
Line regulation | ±1 | % | |||
Current sharing | ±5 | % | |||
Battery output | 250A*2 | ||||
Ripple (Vp-p) | 200 | mv | Rated input/output, with 0.1uF film capacitor and 10uF high frequency electrolyte capacitor, oscilloscope band width of 20MHz. | ||
Output efficiency | 91 | 93 | % | 220Vac input |